DOOR – ENTRY
TITLE: DOOR – ENTRY
DEFICIENCY 1 – UNIT: ENTRY DOOR WILL NOT OPEN
DEFICIENCY CRITERIA: Entry door does not open.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CO HCV – CORRECTION TIMEFRAME: 30 days
RRECTION TIMEFRAME: Within 30 days
DEFICIENCY 2 – UNIT: ENTRY DOOR WILL NOT CLOSE
DEFICIENCY CRITERIA: Entry door does not close (i.e., door seats in frame).
HEALTH AND SAFETY DETERMINATION: Severe Non-Life-Threatening
This is a severe health and safety issue that would cause a serious undue burden on the resident if the deficiency is present for an extended period of time.
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 3 – UNIT: ENTRY DOOR SELF-CLOSING MECHANISM IS DAMAGED, INOPERABLE, OR MISSING
DEFICIENCY CRITERIA: The self-closing mechanism is damaged (i.e., visibly defective; impacts functionality).
OR
The self-closing mechanism does not pull the door closed and engage the latch.
OR
The self-closing mechanism is missing (i.e., evidence of prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 4 – UNIT: ENTRY DOOR’S PRIMARY LOCK IS DAMAGED, INOPERABLE, MISSING, OR NOT INSTALLED
DEFICIENCY CRITERIA: Entry door cannot be secured with a primary lock.
OR
Primary lock is damaged (i.e. impacts functionality) or inoperable with or without visible damage.
OR
Primary lock is missing (i.e. evidence of prior installation, but now not present or incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 5 – UNIT: HOLE, SPLIT, OR CRACK THAT PENETRATES COMPLETELY THROUGH ENTRY DOOR
DEFICIENCY CRITERIA: A hole 1/4" or greater in diameter that penetrates all the way through the door.
OR
A split or crack 1/4" or greater in width that penetrates all the way through the door.
OR
A hole or a crack with separation is present, or the glass is missing within the door, side lites, or transom.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 6 – UNIT: ENTRY DOOR IS MISSING
DEFICIENCY CRITERIA: The entry door is missing.
HEALTH AND SAFETY DETERMINATION: Life-Threatening This is a life-threatening issue requiring a 24-hour repair, correction, or act of abatement.
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 7 – UNIT: ENTRY DOOR SURFACE IS DELAMINATED OR SEPARATED
DEFICIENCY CRITERIA: There is delamination or separation of the door surface 2 inches wide or greater.
OR
There is delamination or separation that affects the integrity of the door (i.e., surface protection or the strength of the door).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 8 – UNIT: ENTRY DOOR FRAME, THRESHOLD, OR TRIM IS DAMAGED OR MISSING
DEFICIENCY CRITERIA: The entry door frame, threshold, or trim is damaged (i.e. visibly defective; impacts functionality).
OR
The entry door frame, threshold, or trim is missing (i.e. evidence of prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
DEFICIENCY 9 – UNIT: ENTRY DOOR SEAL, GASKET, OR STRIPPING IS DAMAGED, INOPERABLE, OR MISSING
DEFICIENCY CRITERIA: The entry door seal, gasket, or stripping is:
- damaged (i.e. visibly defective; impacts functionality);
- inoperable (i.e. overall system or component thereof not meeting function / purpose; with or without visible damage); or
- missing (i.e. evidence of prior installation, but now not present or is incomplete).
AND ONE OF THE FOLLOWING CONDITIONS:
Condition 1:
- General door type: Results in a gap of ¼ inch wide or greater between the door slab and the stop molding on the jamb, or the jamb itself, or between the bottom of the door and the threshold or floor AND permits light around the closed door.
- Special door type: Results in a gap of ¼ inch wide or greater around or under the door or where the doors meet AND permits light around the closed door or where the doors meet.
Condition 2:
- General door type: There is evidence of water penetrating (e.g. water damage or dry rot) around or under the door.
- Special door type: There is evidence of water penetrating (e.g. water damage or dry rot) around or under the door or where the doors meet.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 10 – UNIT: ENTRY DOOR HAS A BROKEN SEAL THERMAL PANE
DEFICIENCY CRITERIA: Entry door has a broken seal thermal pane.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 11 – UNIT: ENTRY DOOR SECURITY DEVICE OR SECONDARY PRIMARY LOCK DAMAGED OR INOPERABLE
DEFICIENCY CRITERIA: The entry door security device or alternative lock is damaged (i.e., visibly defective; impacts functionality).
OR
The entry door security device or alternative lock is inoperable (i.e., overall system or component thereof not meeting function or purpose; with or without visible damage).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
MORE INFORMATION:
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 1 of 42
TITLE: DOOR – ENTRY
VERSION: V1.3
DATE PUBLISHED: 7/31/20
D EFINITION: A hinged, sliding, or revolving barrier at the entrance to the exterior.
PURPOSE: The purpose of the entry door is to:
- Control access to the interior space;
- Protect the health and safety of the resident (e.g., prevent spread of fire or smoke);
- Provide security and privacy (e.g., keep intruders out);
- Provide the resident protection from wind and rain, dampness, hot and cold weather, and infestation;
- Manage the internal atmosphere of the unit (thermal envelope, air quality).
N AME VARIANTS: Exterior unit entry door; Exterior unit access door; Primary door; Exit; Front door
C OMMON MATERIALS: Wood; Metal; Vinyl; Glass; Fiberglass; Composites;
COMMON COMPONENTS: - Door frame (e.g., jamb, header, sill or threshold, stop, seal, weather board [i.e., door sweep], weather stripping, side lights, transom);
- Door slab (e.g., top rail, bottom rail, lock rail, hinge stile, shutting stile, panels, middle panel and muntin);
- Door hardware (e.g., hinge, spring loaded hinge, track, doorknob, door handle, latch, strike/latch plate, pneumatic closer);
- Door locks (e.g., single cylinder dead bolt lock, cylindrical lock, mortice lock, rim lock); Door security devices (e.g. chain-lock, barrel bolt, swing guard, sliding patio door overhead bolt, foot bolt and security bar, bus bar)
LOCATION: Unit Entrance from exterior to interior space
Inside Entrance from exterior to interior space
Outside None
MORE INFORMATION: None
DEFICIENCY 1: Entry door will not open
LOCATION: Unit Inside
DEFICIENCY 2: Entry door will not close
LOCATION: Unit Inside
DEFICIENCY 3: Entry door self-closing mechanism is damaged, inoperable, or missing
LOCATION: Unit Inside
DEFICIENCY 4: Entry door's primary lock is damaged, inoperable, missing, or not installed
LOCATION: Unit Inside
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 2 of 42
DEFICIENCY 5: Hole, split, or crack that penetrates completely through entry door
LOCATION: Unit Inside
DEFICIENCY 6: Entry door is missing
LOCATION: Unit Inside
DEFICIENCY 7: Entry door surface is delaminated or separated
LOCATION: Unit Inside
DEFICIENCY 8: Entry door frame, threshold, or trim is damaged or missing
LOCATION: Unit Inside
DEFICIENCY 9: Entry door seal, gasket, or stripping is damaged, inoperable, or missing
LOCATION: Unit Inside
DEFICIENCY 10: Entry door has a broken seal thermal pane
LOCATION: Unit Inside
DEFICIENCY 11: Entry door security device or secondary primary lock damaged or inoperable
LOCATION: Unit Inside
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 3 of 42
DEFICIENCY 1 – UNIT: ENTRY DOOR WILL NOT OPEN
DEFICIENCY CRITERIA: Entry door does not open.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R2 Safety Indirect Resident could be injured because of this condition.
If entry door will not open, and there is an emergency, then the resident may be in danger of injury or death due to inability to escape / leave home.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not open, then resident cannot reasonably gain access to or leave their home.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not open, then resident cannot reasonably gain access to or leave their home.
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually observe that entry door opens.
REQUEST FOR HELP: - None
ACTION: - Attempt to open the entry door by pulling or pushing on the doorknob and/or handle.
More Information: - None
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 4 of 42
DEFICIENCY 1 – INSIDE: ENTRY DOOR WILL NOT OPEN
DEFICIENCY CRITERIA: Entry door does not open.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R2 Safety Indirect Resident could be injured because of this condition.
If entry door will not open, and there is an emergency, then the resident may be in danger of injury or death due to inability to escape / leave home.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not open, then resident cannot reasonably gain access to or leave their home.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not open, then resident cannot reasonably gain access to or leave their home.
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually observe that entry door opens.
REQUEST FOR HELP: - None
ACTION: - Attempt to open the entry door by pulling or pushing on the doorknob and/or handle.
More Information: - None
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 5 of 42
DEFICIENCY 2 – UNIT: ENTRY DOOR WILL NOT CLOSE
DEFICIENCY CRITERIA: Entry door does not close (i.e., door seats in frame).
HEALTH AND SAFETY DETERMINATION: Severe Non-Life-Threatening
This is a severe health and safety issue that would cause a serious undue burden on the resident if the deficiency is present for an extended period of time.
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Direct Condition could affect resident’s mental, or physical, or psychological state.
If entry door will not close, then resident may experience mental anguish. Also, if entry door will not close, and there is inclement weather, then resident is in danger of excess cold and heat, dampness and mold growth and spread of smoke, fire or poisonous gas which will affect the resident's physical health.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not close, then resident cannot reasonably secure their home from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door will not close, then resident cannot secure their privacy in the home.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not close, then resident is unable to fully use the door, which is expected to be part of their rent.
R7 Increased Monetary Impact to Resident
Indirect Resident would incur additional costs because of this condition.
If entry door will not close, and resident is responsibility for utilities, then resident may experience an increase in utility costs.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door will not close, then it is likely complaint-based work orders are not being addressed.
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually observe that all entry doors close against their frames.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 6 of 42
- Look to see if the entry doors have self-closing mechanisms (e.g., spring loaded hinges or pneumatic closers).
REQUEST FOR HELP: - Ask POA if you have seen all the entry doors to the interior space.
ACTION: - Attempt to close the entry door against the frame.
- If the door has a self-closing mechanism, open the door fully and release.
- Wait for the door to close.
- If it does not self-close, then manually push the door closed against the frame.
- If able to manually close the door, then evaluate the self-closing mechanism under the applicable deficiency within this standard.
More Information: - Look at the edges of the entry door and the jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag inspect the door using the Door - Fire standard.
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 7 of 42
DEFICIENCY 2 – INSIDE: ENTRY DOOR WILL NOT CLOSE
DEFICIENCY CRITERIA: Entry door does not close (i.e., door seats in frame).
HEALTH AND SAFETY DETERMINATION: Severe Non-Life-Threatening
This is a severe health and safety issue that would cause a serious undue burden on the resident if the deficiency is present for an extended period of time.
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Direct Condition could affect resident’s mental, or physical, or psychological state.
If entry door will not close, then resident may experience mental anguish. Also, if entry door will not close, and there is inclement weather, then resident is in danger of excess cold and heat, dampness and mold growth and spread of smoke, fire or poisonous gas which will affect the resident's physical health.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not close, then resident cannot reasonably secure their home from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door will not close, then resident cannot secure their privacy in the home.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not close, then resident is unable to fully use the door, which is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door will not close, then it is likely complaint-based work orders are not being addressed.
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the dwelling unit and locate the entry doors.
- Visually observe that all entry doors close against their frames.
- Look to see if the entry doors have self-closing mechanisms (e.g., spring loaded hinges or pneumatic closers).
REQUEST FOR HELP: - Ask POA if you have seen all the entry doors to the interior space.
ACTION: - Attempt to close the entry door against the frame.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 8 of 42
- If the door has a self-closing mechanism, open the door fully and release.
- Wait for the door to close.
- If it does not self-close, then manually push the door closed against the frame.
- If able to manually close the door, then evaluate the self-closing mechanism under the applicable deficiency within this standard.
More Information: - Look at the edges of the entry door and the jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag inspect the door using the Door - Fire standard.
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 9 of 42
DEFICIENCY 3 – UNIT: ENTRY DOOR SELF-CLOSING MECHANISM IS DAMAGED, INOPERABLE, OR MISSING
DEFICIENCY CRITERIA: The self-closing mechanism is damaged (i.e., visibly defective; impacts functionality).
OR
The self-closing mechanism does not pull the door closed and engage the latch.
OR
The self-closing mechanism is missing (i.e., evidence of prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door self-closer will not pull the door closed and latch, and there is an environmental threat, then resident cannot reasonably assume measures are in place to mitigate exposure.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door self-closer will not pull the door closed and latch, then resident is unable to fully use the door, which is expected to be part of their rent.
INSPECTION PROCESS:
OBSERVATION: - Look to see if the entry door has a self-closing mechanism such as spring-loaded hinges or a pneumatic closer.
REQUEST FOR HELP: - Ask POA if you have seen all the entry doors to the interior space.
ACTION: - Open the door fully and release.
- Wait for the door to self-close and watch and listen for the door to latch.
More Information: - If the entry door does not have a self-closing device, evaluate latch under the applicable deficiency within this standard.
- Look at the edges of the entry door and the jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, evaluate under the Door – Fire standard.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 10 of 42
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 11 of 42
DEFICIENCY 3 – INSIDE: ENTRY DOOR SELF-CLOSING MECHANISM IS DAMAGED, INOPERABLE, OR MISSING
DEFICIENCY CRITERIA: The self-closing mechanism is damaged (i.e., visibly defective; impacts functionality).
OR
The self-closing mechanism does not pull the door closed and engage the latch.
OR
The self-closing mechanism is missing (i.e., evidence of prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door self-closer will not pull the door closed and latch, and there is an environmental threat, then resident cannot reasonably assume measures are in place to mitigate exposure.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door self-closer will not pull the door closed and latch, then resident is unable to fully use the door, which is expected to be part of their rent.
INSPECTION PROCESS:
OBSERVATION: - Look to see if the entry door has a self-closing mechanism such as spring-loaded hinges or a pneumatic closer.
REQUEST FOR HELP: - Ask POA if you have seen all the entry doors to the interior space.
ACTION: - Open the door fully and release.
- Wait for the door to self-close and watch and listen for the door to latch.
More Information: - If the entry door does not have a self-closing device, evaluate latch under the applicable deficiency within this standard.
- Look at the edges of the entry door and the jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, evaluate under the Door – Fire standard.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 12 of 42
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 13 of 42
DEFICIENCY 4 – UNIT: ENTRY DOOR’S PRIMARY LOCK IS DAMAGED, INOPERABLE, MISSING, OR NOT INSTALLED
DEFICIENCY CRITERIA: Entry door cannot be secured with a primary lock.
OR
Primary lock is damaged (i.e. impacts functionality) or inoperable with or without visible damage.
OR
Primary lock is missing (i.e. evidence of prior installation, but now not present or incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not lock, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door will not lock, then resident cannot secure their privacy within the interior spaces.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not lock, then resident is unable to fully use the door, which is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door will not lock, then it is likely complaint-based work orders are not being addressed.
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually observe that all entry doors have a primary lock.
REQUEST FOR HELP: - Ask POA if you have seen all the entry doors to the interior space.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 14 of 42
ACTION: - Close the entry door and engage the primary lock.
- Then, pull the doorknob/handle to ensure that the door is secure.
More Information: - Entry doors are often installed with multiple primary locks; at least one must secure the door.
- If the strike/latch plate is damaged or missing, consider them as part of the locking hardware and inspect under this defect. Other entry door hardware will be addressed under the applicable defect within this standard.
- If additional primary locks or door security devices are present are present inspect under the applicable defect within this standard.
- If one or more is causing a blocked egress record the defect under the Egress standard.
- Look at the edges of the entry door and the jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, evaluate under the Door – Fire standard.
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 15 of 42
DEFICIENCY 4 – INSIDE: ENTRY DOOR’S PRIMARY LOCK IS DAMAGED, INOPERABLE, MISSING, OR NOT INSTALLED
DEFICIENCY CRITERIA: Entry door cannot be secured with a primary lock.
OR
Primary lock is damaged (i.e. impacts functionality) or inoperable with or without visible damage.
OR
Primary lock is missing (i.e. evidence of prior installation, but now not present or incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not lock, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door will not lock, then resident cannot secure their privacy within the interior spaces.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not lock, then resident is unable to fully use the door, which is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door will not lock, then it is likely complaint-based work orders are not being addressed.
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually observe that all entry doors have a primary lock.
REQUEST FOR HELP: - Ask POA if you have seen all the entry doors to the interior space.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 16 of 42
ACTION: - Close the entry door and engage the primary lock.
- Then, pull the doorknob/handle to ensure that the door is secure.
More Information: - Entry doors are often installed with multiple primary locks; at least one must secure the door.
- If the strike/latch plate is damaged or missing, consider them as part of the locking hardware and inspect under this defect. Other entry door hardware will be addressed under the applicable defect within this standard.
- If additional primary locks or door security devices are present are present inspect under the applicable defect within this standard.
- If one or more is causing a blocked egress record the defect under the Egress standard.
- Look at the edges of the entry door and the jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, evaluate under the Door – Fire standard.
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 17 of 42
DEFICIENCY 5 – UNIT: HOLE, SPLIT, OR CRACK THAT PENETRATES COMPLETELY THROUGH ENTRY DOOR
DEFICIENCY CRITERIA: A hole 1/4" or greater in diameter that penetrates all the way through the door.
OR
A split or crack 1/4" or greater in width that penetrates all the way through the door.
OR
A hole or a crack with separation is present, or the glass is missing within the door, side lites, or transom.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door has a hole that penetrates through the door, and there is inclement weather, then resident is in danger of excess cold and heat, dampness and mold growth, and spread of smoke, fire, or poisonous gas, which will affect the resident's physical health.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door has a hole that penetrates through the door, then resident may be in danger of intruders gaining access to the interior space.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door has a hole that penetrates the door, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door has a hole that penetrates through, then resident is unable to fully use a feature of home that is expected to be part of their rent.
R7 Increased Monetary Impact to Resident
Indirect Resident would incur additional costs because of this condition.
If entry door has a hole going through the door, and resident is responsible for utilities, then resident may experience an increase in utility costs.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 18 of 42
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door has a hole that goes completely through the door, then it is likely complaint-based work orders are not being addressed.
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door has a hole that goes completely through the door, then it is likely routine work orders are not being addressed.
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually inspect the surface of the door (i.e. door, lite), looking for any holes, splits, or cracks that entirely penetrate the door, allowing airflow or light into the interior space.
REQUEST FOR HELP: - Ask POA is you have seen all the entry doors to the interior space.
ACTION: - Close the entry door and step back.
- Measure the diameter of any unintended holes and width of splits or cracks.
More Information: - Look at the edges of the entry door and the jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, evaluate under the Door – Fire standard.
- If there is broken glass with sharp edges evaluate it under the Sharp Edges standard.
- If a hole is the result of a missing lock, record under the applicable defect within this standard.
TOOLS OR EQUIPMENT:
REQUIRED: - Flashlight; Inspection mirror; Distance measuring device
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 19 of 42
DEFICIENCY 5 – INSIDE: HOLE, SPLIT, OR CRACK THAT PENETRATES COMPLETELY THROUGH ENTRY DOOR
DEFICIENCY CRITERIA: A hole 1/4" or greater in diameter that penetrates all the way through the door.
OR
A split or crack 1/4" or greater in width that penetrates all the way through the door.
OR
A hole or a crack with separation is present, or the glass is missing within the door, side lites, or transom.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door has a hole that penetrates through the door, and there is inclement weather, then resident is in danger of excess cold and heat, dampness and mold growth, and spread of smoke, fire, or poisonous gas, which will affect the resident's physical health.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door has a hole that penetrates through the door, then resident may be in danger of intruders gaining access to the interior space.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door has a hole that penetrates the door, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door has a hole that penetrates through, then resident is unable to fully use a feature of home that is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door has a hole that goes completely through the door, then it is likely complaint-based work orders are not being addressed.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 20 of 42
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door has a hole that goes completely through the door, then it is likely routine work orders are not being addressed.
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually inspect the surface of the door (i.e. door, lite), looking for any holes, splits, or cracks that entirely penetrate the door, allowing airflow or light into the interior space.
REQUEST FOR HELP: - Ask POA is you have seen all the entry doors to the interior space.
ACTION: - Close the entry door and step back.
- Measure the diameter of any unintended holes and width of splits or cracks.
More Information: - Look at the edges of the entry door and the jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, evaluate under the Door – Fire standard.
- If there is broken glass with sharp edges evaluate it under the Sharp Edges standard.
- If a hole is the result of a missing lock, record under the applicable defect within this standard.
TOOLS OR EQUIPMENT:
REQUIRED: - Flashlight; Inspection mirror; Distance measuring device
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 21 of 42
DEFICIENCY 6 – UNIT: ENTRY DOOR IS MISSING
DEFICIENCY CRITERIA: The entry door is missing.
HEALTH AND SAFETY DETERMINATION: Life-Threatening This is a life-threatening issue requiring a 24-hour repair, correction, or act of abatement.
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 24 hours
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door is missing, and there is inclement weather or an emergency, then the resident's physical health may be in jeopardy.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door is missing, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door is missing, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door is missing, then resident is unable to fully use a feature, which is expected to be part of their rent.
R7 Increased Monetary Impact to Resident
Indirect Resident would incur additional costs because of this condition.
If entry door is missing, and resident is responsibility for utilities, then resident may experience an increase in utility costs due to inability to protect from outside environment.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door is missing, then it is likely complaint-based work orders are not being addressed.
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door is missing, then it is likely routine work orders are not being addressed.
PP1 Market Appeal Direct If this defect occurs, HUD or the property would suffer reputational harm.
If entry door is missing, property visitors will observe the deficiency, which will impact their perception of the property.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 22 of 42
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually inspect for missing entry doors.
REQUEST FOR HELP: - Ask POA is you have seen all the entry doors to the interior space.
ACTION: - Identify any missing entry doors.
More Information: - Look at the edges of the entry door and the jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, evaluate under the Door – Fire standard.
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 23 of 42
DEFICIENCY 6 – INSIDE: ENTRY DOOR IS MISSING
DEFICIENCY CRITERIA: The entry door is missing.
HEALTH AND SAFETY DETERMINATION: Life-Threatening This is a life-threatening issue requiring a 24-hour repair, correction, or act of abatement.
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 24 hours
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door is missing, and there is inclement weather or an emergency, then the resident's physical health may be in jeopardy.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door is missing, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door is missing, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door is missing, then resident is unable to fully use a feature, which is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door is missing, then it is likely complaint-based work orders are not being addressed.
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door is missing, then it is likely routine work orders are not being addressed.
PP1 Market Appeal Direct If this defect occurs, HUD or the property would suffer reputational harm.
If entry door is missing, property visitors will observe the deficiency, which will impact their perception of the property.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 24 of 42
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually inspect for missing entry doors.
REQUEST FOR HELP: - Ask POA is you have seen all the entry doors to the interior space.
ACTION: - Identify any missing entry doors.
More Information: - Look at the edges of the entry door and the jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, evaluate under the Door – Fire standard.
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 25 of 42
DEFICIENCY 7 – UNIT: ENTRY DOOR SURFACE IS DELAMINATED OR SEPARATED
DEFICIENCY CRITERIA: There is delamination or separation of the door surface 2 inches wide or greater.
OR
There is delamination or separation that affects the integrity of the door (i.e., surface protection or the strength of the door).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Direct Condition could affect resident’s mental, or physical, or psychological state.
If an entry door surface is pulling away from the door inner core, then pests (e.g. wasps) may be able to nest in the open space, which could affect the resident's physical health.
R4 Security Indirect Resident cannot control access to unit or property because of this condition.
If there is delamination or separation of the entry door, and it impacts the door's integrity, then intruders may be able to easily access the unit.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If an entry door surface is pulling away from the door's inner core, then infestation (e.g. wasps) may occur in the open space. Resident will likely call this in; may indicate work orders are not being addressed.
PP1 Market Appeal Direct If this defect occurs, HUD or the property would suffer reputational harm.
If the entry door is delaminated or separating, then public or visitor may see this defect, potentially resulting in decreased property reputation.
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually inspect for delamination or separation.
REQUEST FOR HELP: - Ask POA is you have seen all the entry doors to the interior space.
ACTION: - Measure any delamination or separation on the door surface as it sits.
- Determine if any delamination or separation affects the integrity of the door.
More Information: - Look at the edges of the entry door and the door jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, inspect the door using the Door – Fire standard.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 26 of 42
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - Flashlight; Distance measuring device
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 27 of 42
DEFICIENCY 7 – INSIDE: ENTRY DOOR SURFACE IS DELAMINATED OR SEPARATED
DEFICIENCY CRITERIA: There is delamination or separation of the door surface 2 inches wide or greater.
OR
There is delamination or separation that affects the integrity of the door (i.e., surface protection or the strength of the door).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Direct Condition could affect resident’s mental, or physical, or psychological state.
If an entry door surface is pulling away from the door inner core, then pests (e.g. wasps) may be able to nest in the open space, which could affect the resident's physical health.
R4 Security Indirect Resident cannot control access to unit or property because of this condition.
If there is delamination or separation of the entry door, and it impacts the door's integrity, then intruders may be able to easily access the unit.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If an entry door surface is pulling away from the door's inner core, then infestation (e.g. wasps) may occur in the open space. Resident will likely call this in; may indicate work orders are not being addressed.
PP1 Market Appeal Direct If this defect occurs, HUD or the property would suffer reputational harm.
If the entry door is delaminated or separating, then public or visitor may see this defect, potentially resulting in decreased property reputation.
INSPECTION PROCESS:
OBSERVATION: - Look at the entrances to the interior space and locate the entry doors.
- Visually inspect for delamination or separation.
REQUEST FOR HELP: - Ask POA is you have seen all the entry doors to the interior space.
ACTION: - Measure any delamination or separation on the door surface as it sits.
- Determine if any delamination or separation affects the integrity of the door.
More Information: - Look at the edges of the entry door and the door jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, inspect the door using the Door – Fire standard.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 28 of 42
TOOLS OR EQUIPMENT:
REQUIRED: - None
USEFUL: - Flashlight; Distance measuring device
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 29 of 42
DEFICIENCY 8 – UNIT: ENTRY DOOR FRAME, THRESHOLD, OR TRIM IS DAMAGED OR MISSING
DEFICIENCY CRITERIA: The entry door frame, threshold, or trim is damaged (i.e. visibly defective; impacts functionality).
OR
The entry door frame, threshold, or trim is missing (i.e. evidence of prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door frame, threshold or trim is damaged, and there is inclement weather or an emergency, then the resident's physical health may be in jeopardy.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door frame, threshold or trim is damaged or missing, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door frame, threshold, or trim is damaged or missing, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door frame, threshold, or trim is damaged or missing, then resident is unable to fully use a feature, which is expected to be part of their rent.
R7 Increased Monetary Impact to Resident
Indirect Resident would incur additional costs because of this condition.
If entry door frame, threshold, or trim is damaged or missing, and resident is responsibility for utilities, then resident may experience an increase in utility costs due to inability to protect from outside environment.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door frame, threshold, or trim is damaged or missing, then it is likely complaint-based work orders are not being addressed.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 30 of 42
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door frame, threshold, or trim is damaged or missing, then it is likely routine work orders are not being addressed.
INSPECTION PROCESS:
OBSERVATION: - Open the entry doors and observe the door frames.
- Look at the condition of the side jamb, top jamb, threshold, and trim.
REQUEST FOR HELP: - Ask the POA if you have seen all the entry doors.
ACTION: - Inspect the frame, jamb, threshold, and trim for damage (e.g. splits, cracks, holes, rot, gaps, sagging, etc.).
More Information: - Look at the edges of the entry door and the door jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, inspect the door using the Door – Fire standard.
TOOLS OR EQUIPMENT:
REQUIRED: - Flashlight
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 31 of 42
DEFICIENCY 8 – INSIDE: ENTRY DOOR FRAME, THRESHOLD, OR TRIM IS DAMAGED OR MISSING
DEFICIENCY CRITERIA: The entry door frame, threshold, or trim is damaged (i.e. visibly defective; impacts functionality).
OR
The entry door frame, threshold, or trim is missing (i.e. evidence of prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door frame, threshold or trim is damaged, and there is inclement weather or an emergency, then the resident's physical health may be in jeopardy.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door frame, threshold or trim is damaged or missing, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door frame, threshold, or trim is damaged or missing, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door frame, threshold, or trim is damaged or missing, then resident is unable to fully use a feature, which is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door frame, threshold, or trim is damaged or missing, then it is likely complaint-based work orders are not being addressed.
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door frame, threshold, or trim is damaged or missing, then it is likely routine work orders are not being addressed.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 32 of 42
INSPECTION PROCESS:
OBSERVATION: - Open the entry doors and observe the door frames.
- Look at the condition of the side jamb, top jamb, threshold, and trim.
REQUEST FOR HELP: - Ask the POA if you have seen all the entry doors.
ACTION: - Inspect the frame, jamb, threshold, and trim for damage (e.g. splits, cracks, holes, rot, gaps, sagging, etc.).
More Information: - Look at the edges of the entry door and the door jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, inspect the door using the Door – Fire standard.
TOOLS OR EQUIPMENT:
REQUIRED: - Flashlight
USEFUL: - None
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 33 of 42
DEFICIENCY 9 – UNIT: ENTRY DOOR SEAL, GASKET, OR STRIPPING IS DAMAGED, INOPERABLE, OR MISSING
DEFICIENCY CRITERIA: The entry door seal, gasket, or stripping is:
- damaged (i.e. visibly defective; impacts functionality);
- inoperable (i.e. overall system or component thereof not meeting function / purpose; with or without visible damage); or
- missing (i.e. evidence of prior installation, but now not present or is incomplete).
AND ONE OF THE FOLLOWING CONDITIONS:
Condition 1:
- General door type: Results in a gap of ¼ inch wide or greater between the door slab and the stop molding on the jamb, or the jamb itself, or between the bottom of the door and the threshold or floor AND permits light around the closed door.
- Special door type: Results in a gap of ¼ inch wide or greater around or under the door or where the doors meet AND permits light around the closed door or where the doors meet.
Condition 2:
- General door type: There is evidence of water penetrating (e.g. water damage or dry rot) around or under the door.
- Special door type: There is evidence of water penetrating (e.g. water damage or dry rot) around or under the door or where the doors meet.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door seal, gasket, or stripping is damaged, inoperable, or missing and there is inclement weather or an emergency (e.g. smoke or fire spread), then the resident's physical health may be in jeopardy.
R7 Increased Monetary Impact to Resident
Indirect Resident would incur additional costs because of this condition.
If entry door seal, gasket, or stripping is damaged, inoperable, or missing, and resident is responsible for utilities, then resident may experience an increase in utility costs due to inability to protect from outside environment.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 34 of 42
INSPECTION PROCESS:
OBSERVATION: General door type:
- With door open, inspect the top and sides of the jamb for damaged, inoperable, or missing seal / gasket / stripping (e.g. splits, cracks, holes, gaps, etc.).
- With door open, inspect the bottom door sweep for damaged, inoperable, or missing seal / gasket / stripping.
- Standing inside the unit with door closed, look for light around and under.
- Standing inside the unit with door closed, identify any gap around the door.
Special door type:
- With door open, inspect the top and sides of the jamb for damaged, inoperable, or missing seal / gasket / stripping (e.g. splits, cracks, holes, gaps, etc.).
- With door open, inspect the bottom door sweep for damaged, inoperable, or missing seal / gasket / stripping.
- With door open, inspect for damaged, inoperable, or missing seal / gasket / stripping where the doors meet.
- Standing inside the unit with door closed, look for light around and under the door and where the doors meet (i.e. astragal).
- Standing inside the unit with door closed, identify any gap around the door.
REQUEST FOR HELP: - Ask the POA if you have seen all the entry doors.
ACTION: General door type:
- Measure the gap between the edge of the door slab and the stop molding or the jamb.
- Measure the gap between the bottom of the door and the threshold or the floor.
Special door type:
- Measure the gap between the edge of the door slab and the stop molding or the jamb.
- Measure the gap between the bottom of the door and the threshold or the floor.
- Measure the gap where the doors meet.
More Information: - This defect includes both manufacture installed and after market seals, gaskets, or stripping.
- Entry doors designed without a seal / gasket / stripping are not considered a defect.
- To determine this, use a mirror to look at the top, sides, and bottom of the door and the top and sides of the jamb for evidence that a seal / gasket / stripping was ever present (e.g. adhesive residue, open staple, nail or screw holes, empty kerf, etc.).
- For example, there is a gap less than 1/4 inch permitting light under a entry door, but no evidence of water penetration (e.g. water damage or dry rot). Using touch or a mirror it is determined that the door was designed without a seal or a threshold. In this case, there is not a defect. However, if there is evidence of water penetration, then it would be considered a defect.
- Look at the edges of the entry door and the door jamb or frame for a tag indicating that the door is a fire door.
- If it has a tag, inspect the door using the Door – Fire standard.
TOOLS OR EQUIPMENT:
REQUIRED: -
TITLE: DOOR – ENTRY
DEFICIENCY 1 – UNIT: ENTRY DOOR WILL NOT OPEN
DEFICIENCY CRITERIA: Entry door does not open.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CO HCV – CORRECTION TIMEFRAME: 30 days
RRECTION TIMEFRAME: Within 30 days
DEFICIENCY 2 – UNIT: ENTRY DOOR WILL NOT CLOSE
DEFICIENCY CRITERIA: Entry door does not close (i.e., door seats in frame).
HEALTH AND SAFETY DETERMINATION: Severe Non-
This is a severe health and safety issue that would cause a serious undue burden on the resident if the deficiency is present for an extended period of time.
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 3 – UNIT: ENTRY DOOR SELF-
DEFICIENCY CRITERIA: The self-
OR
The self-
OR
The self-
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 4 – UNIT: ENTRY DOOR’S PRIMARY LOCK IS DAMAGED, INOPERABLE, MISSING, OR NOT INSTALLED
DEFICIENCY CRITERIA: Entry door cannot be secured with a primary lock.
OR
Primary lock is damaged (i.e. impacts functionality) or inoperable with or without visible damage.
OR
Primary lock is missing (i.e. evidence of prior installation, but now not present or incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 5 – UNIT: HOLE, SPLIT, OR CRACK THAT PENETRATES COMPLETELY THROUGH ENTRY DOOR
DEFICIENCY CRITERIA: A hole 1/4" or greater in diameter that penetrates all the way through the door.
OR
A split or crack 1/4" or greater in width that penetrates all the way through the door.
OR
A hole or a crack with separation is present, or the glass is missing within the door, side lites, or transom.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 6 – UNIT: ENTRY DOOR IS MISSING
DEFICIENCY CRITERIA: The entry door is missing.
HEALTH AND SAFETY DETERMINATION: Life-
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 7 – UNIT: ENTRY DOOR SURFACE IS DELAMINATED OR SEPARATED
DEFICIENCY CRITERIA: There is delamination or separation of the door surface 2 inches wide or greater.
OR
There is delamination or separation that affects the integrity of the door (i.e., surface protection or the strength of the door).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 8 – UNIT: ENTRY DOOR FRAME, THRESHOLD, OR TRIM IS DAMAGED OR MISSING
DEFICIENCY CRITERIA: The entry door frame, threshold, or trim is damaged (i.e. visibly defective; impacts functionality).
OR
The entry door frame, threshold, or trim is missing (i.e. evidence of prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
DEFICIENCY 9 – UNIT: ENTRY DOOR SEAL, GASKET, OR STRIPPING IS DAMAGED, INOPERABLE, OR MISSING
DEFICIENCY CRITERIA: The entry door seal, gasket, or stripping is:
-
-
-
AND ONE OF THE FOLLOWING CONDITIONS:
Condition 1:
-
-
Condition 2:
-
-
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 10 – UNIT: ENTRY DOOR HAS A BROKEN SEAL THERMAL PANE
DEFICIENCY CRITERIA: Entry door has a broken seal thermal pane.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 11 – UNIT: ENTRY DOOR SECURITY DEVICE OR SECONDARY PRIMARY LOCK DAMAGED OR INOPERABLE
DEFICIENCY CRITERIA: The entry door security device or alternative lock is damaged (i.e., visibly defective; impacts functionality).
OR
The entry door security device or alternative lock is inoperable (i.e., overall system or component thereof not meeting function or purpose; with or without visible damage).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: 30 days
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 1 of 42
TITLE: DOOR – ENTRY
VERSION: V1.3
DATE PUBLISHED: 7/31/20
D EFINITION: A hinged, sliding, or revolving barrier at the entrance to the exterior.
PURPOSE: The purpose of the entry door is to:
-
-
-
-
-
N AME VARIANTS: Exterior unit entry door; Exterior unit access door; Primary door; Exit; Front door
C OMMON MATERIALS: Wood; Metal; Vinyl; Glass; Fiberglass; Composites;
COMMON COMPONENTS: -
-
-
-
LOCATION: Unit Entrance from exterior to interior space
Inside Entrance from exterior to interior space
Outside None
MORE INFORMATION: None
DEFICIENCY 1: Entry door will not open
LOCATION: Unit Inside
DEFICIENCY 2: Entry door will not close
LOCATION: Unit Inside
DEFICIENCY 3: Entry door self-
LOCATION: Unit Inside
DEFICIENCY 4: Entry door's primary lock is damaged, inoperable, missing, or not installed
LOCATION: Unit Inside
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 2 of 42
DEFICIENCY 5: Hole, split, or crack that penetrates completely through entry door
LOCATION: Unit Inside
DEFICIENCY 6: Entry door is missing
LOCATION: Unit Inside
DEFICIENCY 7: Entry door surface is delaminated or separated
LOCATION: Unit Inside
DEFICIENCY 8: Entry door frame, threshold, or trim is damaged or missing
LOCATION: Unit Inside
DEFICIENCY 9: Entry door seal, gasket, or stripping is damaged, inoperable, or missing
LOCATION: Unit Inside
DEFICIENCY 10: Entry door has a broken seal thermal pane
LOCATION: Unit Inside
DEFICIENCY 11: Entry door security device or secondary primary lock damaged or inoperable
LOCATION: Unit Inside
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 3 of 42
DEFICIENCY 1 – UNIT: ENTRY DOOR WILL NOT OPEN
DEFICIENCY CRITERIA: Entry door does not open.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R2 Safety Indirect Resident could be injured because of this condition.
If entry door will not open, and there is an emergency, then the resident may be in danger of injury or death due to inability to escape / leave home.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not open, then resident cannot reasonably gain access to or leave their home.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not open, then resident cannot reasonably gain access to or leave their home.
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
ACTION: -
More Information: -
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 4 of 42
DEFICIENCY 1 – INSIDE: ENTRY DOOR WILL NOT OPEN
DEFICIENCY CRITERIA: Entry door does not open.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R2 Safety Indirect Resident could be injured because of this condition.
If entry door will not open, and there is an emergency, then the resident may be in danger of injury or death due to inability to escape / leave home.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not open, then resident cannot reasonably gain access to or leave their home.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not open, then resident cannot reasonably gain access to or leave their home.
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
ACTION: -
More Information: -
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 5 of 42
DEFICIENCY 2 – UNIT: ENTRY DOOR WILL NOT CLOSE
DEFICIENCY CRITERIA: Entry door does not close (i.e., door seats in frame).
HEALTH AND SAFETY DETERMINATION: Severe Non-
This is a severe health and safety issue that would cause a serious undue burden on the resident if the deficiency is present for an extended period of time.
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Direct Condition could affect resident’s mental, or physical, or psychological state.
If entry door will not close, then resident may experience mental anguish. Also, if entry door will not close, and there is inclement weather, then resident is in danger of excess cold and heat, dampness and mold growth and spread of smoke, fire or poisonous gas which will affect the resident's physical health.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not close, then resident cannot reasonably secure their home from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door will not close, then resident cannot secure their privacy in the home.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not close, then resident is unable to fully use the door, which is expected to be part of their rent.
R7 Increased Monetary Impact to Resident
Indirect Resident would incur additional costs because of this condition.
If entry door will not close, and resident is responsibility for utilities, then resident may experience an increase in utility costs.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door will not close, then it is likely complaint-
INSPECTION PROCESS:
OBSERVATION: -
-
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 6 of 42
-
REQUEST FOR HELP: -
ACTION: -
-
-
-
-
More Information: -
-
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 7 of 42
DEFICIENCY 2 – INSIDE: ENTRY DOOR WILL NOT CLOSE
DEFICIENCY CRITERIA: Entry door does not close (i.e., door seats in frame).
HEALTH AND SAFETY DETERMINATION: Severe Non-
This is a severe health and safety issue that would cause a serious undue burden on the resident if the deficiency is present for an extended period of time.
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Direct Condition could affect resident’s mental, or physical, or psychological state.
If entry door will not close, then resident may experience mental anguish. Also, if entry door will not close, and there is inclement weather, then resident is in danger of excess cold and heat, dampness and mold growth and spread of smoke, fire or poisonous gas which will affect the resident's physical health.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not close, then resident cannot reasonably secure their home from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door will not close, then resident cannot secure their privacy in the home.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not close, then resident is unable to fully use the door, which is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door will not close, then it is likely complaint-
INSPECTION PROCESS:
OBSERVATION: -
-
-
REQUEST FOR HELP: -
ACTION: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 8 of 42
-
-
-
-
More Information: -
-
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 9 of 42
DEFICIENCY 3 – UNIT: ENTRY DOOR SELF-
DEFICIENCY CRITERIA: The self-
OR
The self-
OR
The self-
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door self-
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door self-
INSPECTION PROCESS:
OBSERVATION: -
REQUEST FOR HELP: -
ACTION: -
-
More Information: -
-
-
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 10 of 42
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 11 of 42
DEFICIENCY 3 – INSIDE: ENTRY DOOR SELF-
DEFICIENCY CRITERIA: The self-
OR
The self-
OR
The self-
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door self-
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door self-
INSPECTION PROCESS:
OBSERVATION: -
REQUEST FOR HELP: -
ACTION: -
-
More Information: -
-
-
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 12 of 42
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 13 of 42
DEFICIENCY 4 – UNIT: ENTRY DOOR’S PRIMARY LOCK IS DAMAGED, INOPERABLE, MISSING, OR NOT INSTALLED
DEFICIENCY CRITERIA: Entry door cannot be secured with a primary lock.
OR
Primary lock is damaged (i.e. impacts functionality) or inoperable with or without visible damage.
OR
Primary lock is missing (i.e. evidence of prior installation, but now not present or incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not lock, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door will not lock, then resident cannot secure their privacy within the interior spaces.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not lock, then resident is unable to fully use the door, which is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door will not lock, then it is likely complaint-
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 14 of 42
ACTION: -
-
More Information: -
-
-
-
-
-
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 15 of 42
DEFICIENCY 4 – INSIDE: ENTRY DOOR’S PRIMARY LOCK IS DAMAGED, INOPERABLE, MISSING, OR NOT INSTALLED
DEFICIENCY CRITERIA: Entry door cannot be secured with a primary lock.
OR
Primary lock is damaged (i.e. impacts functionality) or inoperable with or without visible damage.
OR
Primary lock is missing (i.e. evidence of prior installation, but now not present or incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door will not lock, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door will not lock, then resident cannot secure their privacy within the interior spaces.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door will not lock, then resident is unable to fully use the door, which is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door will not lock, then it is likely complaint-
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 16 of 42
ACTION: -
-
More Information: -
-
-
-
-
-
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 17 of 42
DEFICIENCY 5 – UNIT: HOLE, SPLIT, OR CRACK THAT PENETRATES COMPLETELY THROUGH ENTRY DOOR
DEFICIENCY CRITERIA: A hole 1/4" or greater in diameter that penetrates all the way through the door.
OR
A split or crack 1/4" or greater in width that penetrates all the way through the door.
OR
A hole or a crack with separation is present, or the glass is missing within the door, side lites, or transom.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door has a hole that penetrates through the door, and there is inclement weather, then resident is in danger of excess cold and heat, dampness and mold growth, and spread of smoke, fire, or poisonous gas, which will affect the resident's physical health.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door has a hole that penetrates through the door, then resident may be in danger of intruders gaining access to the interior space.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door has a hole that penetrates the door, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door has a hole that penetrates through, then resident is unable to fully use a feature of home that is expected to be part of their rent.
R7 Increased Monetary Impact to Resident
Indirect Resident would incur additional costs because of this condition.
If entry door has a hole going through the door, and resident is responsible for utilities, then resident may experience an increase in utility costs.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 18 of 42
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door has a hole that goes completely through the door, then it is likely complaint-
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door has a hole that goes completely through the door, then it is likely routine work orders are not being addressed.
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
ACTION: -
-
More Information: -
-
-
-
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 19 of 42
DEFICIENCY 5 – INSIDE: HOLE, SPLIT, OR CRACK THAT PENETRATES COMPLETELY THROUGH ENTRY DOOR
DEFICIENCY CRITERIA: A hole 1/4" or greater in diameter that penetrates all the way through the door.
OR
A split or crack 1/4" or greater in width that penetrates all the way through the door.
OR
A hole or a crack with separation is present, or the glass is missing within the door, side lites, or transom.
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door has a hole that penetrates through the door, and there is inclement weather, then resident is in danger of excess cold and heat, dampness and mold growth, and spread of smoke, fire, or poisonous gas, which will affect the resident's physical health.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door has a hole that penetrates through the door, then resident may be in danger of intruders gaining access to the interior space.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door has a hole that penetrates the door, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door has a hole that penetrates through, then resident is unable to fully use a feature of home that is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door has a hole that goes completely through the door, then it is likely complaint-
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 20 of 42
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door has a hole that goes completely through the door, then it is likely routine work orders are not being addressed.
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
ACTION: -
-
More Information: -
-
-
-
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 21 of 42
DEFICIENCY 6 – UNIT: ENTRY DOOR IS MISSING
DEFICIENCY CRITERIA: The entry door is missing.
HEALTH AND SAFETY DETERMINATION: Life-
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 24 hours
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door is missing, and there is inclement weather or an emergency, then the resident's physical health may be in jeopardy.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door is missing, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door is missing, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door is missing, then resident is unable to fully use a feature, which is expected to be part of their rent.
R7 Increased Monetary Impact to Resident
Indirect Resident would incur additional costs because of this condition.
If entry door is missing, and resident is responsibility for utilities, then resident may experience an increase in utility costs due to inability to protect from outside environment.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door is missing, then it is likely complaint-
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door is missing, then it is likely routine work orders are not being addressed.
PP1 Market Appeal Direct If this defect occurs, HUD or the property would suffer reputational harm.
If entry door is missing, property visitors will observe the deficiency, which will impact their perception of the property.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 22 of 42
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
ACTION: -
More Information: -
-
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 23 of 42
DEFICIENCY 6 – INSIDE: ENTRY DOOR IS MISSING
DEFICIENCY CRITERIA: The entry door is missing.
HEALTH AND SAFETY DETERMINATION: Life-
CORRECTION TIMEFRAME: 24 hours
HCV – CORRECTION TIMEFRAME: 24 hours
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door is missing, and there is inclement weather or an emergency, then the resident's physical health may be in jeopardy.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door is missing, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door is missing, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door is missing, then resident is unable to fully use a feature, which is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door is missing, then it is likely complaint-
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door is missing, then it is likely routine work orders are not being addressed.
PP1 Market Appeal Direct If this defect occurs, HUD or the property would suffer reputational harm.
If entry door is missing, property visitors will observe the deficiency, which will impact their perception of the property.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 24 of 42
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
ACTION: -
More Information: -
-
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 25 of 42
DEFICIENCY 7 – UNIT: ENTRY DOOR SURFACE IS DELAMINATED OR SEPARATED
DEFICIENCY CRITERIA: There is delamination or separation of the door surface 2 inches wide or greater.
OR
There is delamination or separation that affects the integrity of the door (i.e., surface protection or the strength of the door).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Direct Condition could affect resident’s mental, or physical, or psychological state.
If an entry door surface is pulling away from the door inner core, then pests (e.g. wasps) may be able to nest in the open space, which could affect the resident's physical health.
R4 Security Indirect Resident cannot control access to unit or property because of this condition.
If there is delamination or separation of the entry door, and it impacts the door's integrity, then intruders may be able to easily access the unit.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If an entry door surface is pulling away from the door's inner core, then infestation (e.g. wasps) may occur in the open space. Resident will likely call this in; may indicate work orders are not being addressed.
PP1 Market Appeal Direct If this defect occurs, HUD or the property would suffer reputational harm.
If the entry door is delaminated or separating, then public or visitor may see this defect, potentially resulting in decreased property reputation.
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
ACTION: -
-
More Information: -
-
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 26 of 42
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 27 of 42
DEFICIENCY 7 – INSIDE: ENTRY DOOR SURFACE IS DELAMINATED OR SEPARATED
DEFICIENCY CRITERIA: There is delamination or separation of the door surface 2 inches wide or greater.
OR
There is delamination or separation that affects the integrity of the door (i.e., surface protection or the strength of the door).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Direct Condition could affect resident’s mental, or physical, or psychological state.
If an entry door surface is pulling away from the door inner core, then pests (e.g. wasps) may be able to nest in the open space, which could affect the resident's physical health.
R4 Security Indirect Resident cannot control access to unit or property because of this condition.
If there is delamination or separation of the entry door, and it impacts the door's integrity, then intruders may be able to easily access the unit.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If an entry door surface is pulling away from the door's inner core, then infestation (e.g. wasps) may occur in the open space. Resident will likely call this in; may indicate work orders are not being addressed.
PP1 Market Appeal Direct If this defect occurs, HUD or the property would suffer reputational harm.
If the entry door is delaminated or separating, then public or visitor may see this defect, potentially resulting in decreased property reputation.
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
ACTION: -
-
More Information: -
-
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 28 of 42
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 29 of 42
DEFICIENCY 8 – UNIT: ENTRY DOOR FRAME, THRESHOLD, OR TRIM IS DAMAGED OR MISSING
DEFICIENCY CRITERIA: The entry door frame, threshold, or trim is damaged (i.e. visibly defective; impacts functionality).
OR
The entry door frame, threshold, or trim is missing (i.e. evidence of prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door frame, threshold or trim is damaged, and there is inclement weather or an emergency, then the resident's physical health may be in jeopardy.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door frame, threshold or trim is damaged or missing, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door frame, threshold, or trim is damaged or missing, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door frame, threshold, or trim is damaged or missing, then resident is unable to fully use a feature, which is expected to be part of their rent.
R7 Increased Monetary Impact to Resident
Indirect Resident would incur additional costs because of this condition.
If entry door frame, threshold, or trim is damaged or missing, and resident is responsibility for utilities, then resident may experience an increase in utility costs due to inability to protect from outside environment.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door frame, threshold, or trim is damaged or missing, then it is likely complaint-
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 30 of 42
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door frame, threshold, or trim is damaged or missing, then it is likely routine work orders are not being addressed.
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
ACTION: -
More Information: -
-
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 31 of 42
DEFICIENCY 8 – INSIDE: ENTRY DOOR FRAME, THRESHOLD, OR TRIM IS DAMAGED OR MISSING
DEFICIENCY CRITERIA: The entry door frame, threshold, or trim is damaged (i.e. visibly defective; impacts functionality).
OR
The entry door frame, threshold, or trim is missing (i.e. evidence of prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door frame, threshold or trim is damaged, and there is inclement weather or an emergency, then the resident's physical health may be in jeopardy.
R4 Security Direct Resident cannot control access to unit or property because of this condition.
If entry door frame, threshold or trim is damaged or missing, then resident cannot reasonably secure the property from intruders.
R5 Privacy Direct Condition limits the resident’s reasonable expectation of privacy in their dwelling.
If entry door frame, threshold, or trim is damaged or missing, then resident cannot secure their privacy within the interior space.
R6 Usability and Operability of Fixtures
Direct Because of this condition, the resident is unable to use certain fixtures, features, or appliances, which are reasonably assumed to be part of their rent.
If entry door frame, threshold, or trim is damaged or missing, then resident is unable to fully use a feature, which is expected to be part of their rent.
M1 Corrective Maintenance
Direct It is reasonable to expect a tenant to report this deficiency, and for facilities management to prioritize a work order response to fix that deficiency.
If the entry door frame, threshold, or trim is damaged or missing, then it is likely complaint-
M2 Routine Maintenance
Direct It is reasonable to expect that this deficiency would be identified through routine daily observations and facilities management would prioritize work orders to fix this deficiency.
If the entry door frame, threshold, or trim is damaged or missing, then it is likely routine work orders are not being addressed.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 32 of 42
INSPECTION PROCESS:
OBSERVATION: -
-
REQUEST FOR HELP: -
ACTION: -
More Information: -
-
TOOLS OR EQUIPMENT:
REQUIRED: -
USEFUL: -
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 33 of 42
DEFICIENCY 9 – UNIT: ENTRY DOOR SEAL, GASKET, OR STRIPPING IS DAMAGED, INOPERABLE, OR MISSING
DEFICIENCY CRITERIA: The entry door seal, gasket, or stripping is:
-
-
-
AND ONE OF THE FOLLOWING CONDITIONS:
Condition 1:
-
-
Condition 2:
-
-
HEALTH AND SAFETY DETERMINATION: Standard This is a standard health and safety issue. A repair, correction, or act of abatement for this deficiency should occur within 30 days.
CORRECTION TIMEFRAME: Within 30 days
HCV – CORRECTION TIMEFRAME: Within 30 days
RATIONALE:
CODE CATEGORY TYPE DESCRIPTION EXPLANATION
R1 Health Indirect Condition could affect resident’s mental, or physical, or psychological state.
If entry door seal, gasket, or stripping is damaged, inoperable, or missing and there is inclement weather or an emergency (e.g. smoke or fire spread), then the resident's physical health may be in jeopardy.
R7 Increased Monetary Impact to Resident
Indirect Resident would incur additional costs because of this condition.
If entry door seal, gasket, or stripping is damaged, inoperable, or missing, and resident is responsible for utilities, then resident may experience an increase in utility costs due to inability to protect from outside environment.
NATIONAL STANDARDS FOR THE PHYSICAL INSPECTION OF REAL ESTATE
U .S. DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT Page 34 of 42
INSPECTION PROCESS:
OBSERVATION: General door type:
-
-
-
-
Special door type:
-
-
-
-
-
REQUEST FOR HELP: -
ACTION: General door type:
-
-
Special door type:
-
-
-
More Information: -
-
-
-
-
-
TOOLS OR EQUIPMENT:
REQUIRED: -